Special Tool - Hand Tester: 57001-1394
Crankshaft Sensor Resistance
Connections:
Meter (+) → Y lead
Meter (–) → BK lead
Standard: 376
564 Ω

If there is more resistance than the specified value, the coil has an open lead and must be replaced. Much less than this resistance means the coil is shorted, and must be replaced.
Any tester reading less than infinity (∞) indicates a short, necessitating replacement of the crankshaft sensor.
Crankshaft Sensor Installation
Crankshaft Sensor Peak Voltage InspectionWarning Symbols
: The red
warning indicator light
and the oil pressure warning symbol
( )
goes on whenever the oil pressure
is dangerously low or the ignition switch is in the “ON� position with the
engine not running, and go off when the
engine oil pressure is high enough. Refer
to the Mainten ...
Check 3-7 Stop Watch Inspection
Connect the leads in the same circuit as Check 3-2.
By pushing the upper button each time to set the stop
watch mode.
Connect the insulated auxiliary lead processed insulation
to the terminal [13] as shown in the figure, then stop watch
start to count.
While count the stop watch, conn ...
Main Throttle Sensor Output Voltage Inspection
Measure the output voltage at the main throttle sensor in
the same way as input voltage inspection, note the following.
Disconnect the main throttle sensor connector and connect
the setting adapter [A] between these connectors.
Special Tool - Throttle Sensor Setting Adapter: 57001
-15 ...