Special Tool - Hand Tester: 57001-1394
If there is a high resistance or no reading (∞) between any two segments, a winding is open and the starter motor must be replaced.
If there is any reading at all, the armature has a short and the starter motor must be replaced.

NOTE
Even if the foregoing checks show the armature to be good, it may be defective in some manner not readily detectable with the hand tester. If all other starter motor and starter motor circuit components check good, but the starter motor still does not turn over or only turns over weakly, replace the starter motor with a new one.
Commutator Cleaning and Inspection
Brush Lead InspectionStick Coil Removal
Remove the air cleaner housing (see Air Cleaner Housing
Removal in the Fuel System (DFI) chapter).
Disconnect the stick coil connectors [A].
Pull out the stick coils [B] upward.
First, turn the stick coil by 90 degrees, and then pull it out
by twisting the coil head to the left and righ ...
Radiator Fan System
Fan Motor Inspection
Remove the air cleaner housing (see Air Cleaner Housing
Removal in the Fuel System (DFI) chapter).
Disconnect the connector [A].
Using an auxiliary leads, supply battery power to the fan
motor.
If the fan does not rotate, the fan motor is defective and
must be re ...
Unit Setting
The unit setting in the meter instrument
can be changed according to local
regulations. Make sure the unit setting
is correctly displayed before riding.
A. Speedometer
B. Meter Display Units
NOTE
Do not operate the motorcycle with
wrong unit (mph or km/h) of the
speedometer.
To change ...